How Charging the Lead Acid Battery(4)? How Charging the Lead Acid Battery(4)? Whereas the voltage settings in Figure 4-4 apply to low-pressure lead acid batteries with a pressure relief valve setting of about 34 kPa (5 psi), the cylindrical SLA by Hawker requires higher voltage settings. These voltage limits should be set according to the manufacturerâs specifications. Failing to apply the recommended voltage threshold for these batteries causes a gradual decrease in capacity due to sulfation. Typically, the Hawker cell has a pressure relief setting of 345 kPa (50 psi). This allows some recombination of the gases during charge. An SLA must be stored in a charged state. A topping View the rest of this article